Technical data VICTRIX PRO 180 V2 EU

Code 3.033864
custom Array
custom2 Array
C.H. Energy class A
Heat output ref. 80-60°C kW 166,9
Heat output ref. 50-30°C kW 180,2
Efficiency at nominal heat output ref. 80-60 °C 98,2%
Efficiency at nominal heat output ref. 50-30 °C 106,0%
Dimensions (HxWxD) mm 1098 (1232) x 600 x 557
Modulating heat output 20 - 100%

Technical data VICTRIX PRO 180 V2 EU

Code 3.033864
Product plus HYDROGEN READY 20%
Product plus BIM READY
C.H. Energy class A
Heat output ref. 80-60°C kW 166,9
Heat output ref. 50-30°C kW 180,2
Efficiency at nominal heat output ref. 80-60 °C 98,2%
Efficiency at nominal heat output ref. 50-30 °C 106,0%
Dimensions (HxWxD) mm 1098 (1232) x 600 x 557
Modulating heat output 20 - 100%

Gallery

Wall hung, modular condensing boiler for heating only. 

Wide modulating ratio up to 5 boilers in cascade installation, high performances with reduced consumption thanks to the 1:10 modulation range and high efficiency, the new VICTRIX PRO V2 is the ideal solution for light commercial solutions in residential and commercial buildings. The new design, compact and linear, with a vertical sliding door protecting the control board, makes its installation easy even in residential buildings (according to the current regulations in force in each country).
Certified for indoor and outdoor installations, even in unsheltered areas thanks to the IPX5D electric protection, the boiler is supplied with the -5 °C anti-freeze kit as standard.
Thanks to low emissions of carbon monoxide (CO) and nitrogen oxide (NOX), VICTRIX PRO V2 belongs to class 6, the most environmentally-friendly class established by the European standards (UNI EN 297 e UNI EN 483).

The new VICTRIX PRO V2 can work with natural gas, LPG and up to 20% blend of hydrogen.

...

CRONO 7 (weekly digital chronothermostat)   Cod.3.021622

ON/OFF room thermostat.

 

Class of device IV* or VII

Contribution to the environmental heating seasonal energy efficiency 2%* or 3,5%

* default settings

...

CRONO 7 WIRELESS (wireless weekly digital chronothermostat)   Cod.3.021624

Wireless ON/OFF room thermostat.

 

Class of device IV* or VII

Contribution to the environmental heating energy efficiency 2%* or 3,5%

* default settings

...

Cascade and zone regulator kit   Cod.3.034119

It can manage 3 water distribution zones plus an external storage tank unit
and thermal solar for DHW production, both in standalone and cascade
configurations. It includes power supply connection for installation on a DIN
rail.

...

Clip-in for VICTRIX PRO V2   Cod.3.034122

To be used together with Cascade and Zones regulator kit (1 for each boiler).

...

Expansion kit for Cascade and Zones regulator kit   Cod.3.034124

To be used to manage 1 additional zone (direct or mixed) up to a maximum
of 5.

...

External probe   Cod.3.015266

For single installation of VICTRIX PRO V2.
For MAGIS COMBO V2, MAGIS PRO V2, MAGIS COMBO PLUS V2, MAGIS HERCULES PRO, MAGIS HERCULES PRO MINI/EH, TRIO PACK ELECTRIC, TRIO HYDRO system ELECTRIC and MAGIS M/EH.

Temperature control class II*, VI or VII
Contribution to seasonal space heating energy efficiency 2%*, 4 or 3,5%

* default settings

...

External probe kit (for cascade installation)   Cod.3.024511

Paired with cascade and zone regulator kit, it optimizes energy
consumption by adjusting the plant delivery temperature for variable
temperature functioning 

...

Flow probe kit   Cod.3.015267

To be located on the delivery side of the plant, after the hydraulic
separator, it allows the cascade and zone regulator to manage the
delivery temperature of the plant or of the mixed zones available

...

Remote control for single VICTRIX PRO V2   Cod.3.020358

This is a modulating control unit that serves to optimize climatic
management of the temperature in rooms.
It can only be used on systems with a single temperature control.

...

System delivery probe kit for the boiler VICTRIX PRO V2   Cod.3.024245

Connected to the boiler board, it measures the delivery temperature after the hydraulic manifold.

...

Tele-management kit 2.0   Cod.3.034121

It works together with the Cascade and Zones regulator kit. It allows remote
management of the device with a dedicated APP.

...

Zone manager kit   Cod.3.034120

Modulating temperature control, backlit display and remote management of
the zone. It works together with the Cascade and Zones regulator kit.

...

4 extension pipes Ø 160 kit   Cod.3.034559

For VICTRIX PRO 180 V2 0,5 m long

...

4 extension pipes Ø 160 kit   Cod.3.034560

For VICTRIX PRO 180 V2 1 m long

...

4 extension pipes Ø 160 kit   Cod.3.034561

For VICTRIX PRO 180 V2 2 m long

...

4 x 90° bends Ø 160 kit   Cod.3.034563

For VICTRIX PRO 180 V2

...

45° bend Ø 160 kit   Cod.3.034562

For VICTRIX PRO 180 V2 

...

Horizontal kit Ø 160   Cod.3.034556

For VICTRIX PRO 180 V2 (to discharge in the chimney)

...

Horizontal kit Ø 160   Cod.3.034557

For VICTRIX PRO 180 V2 (to discharge horizontally)

...

Stub-pipe kit Ø160 for air intake   Cod.3.034565

for VICTRIX PRO 180 V2 with B23 configuration

...

Terminal vertical outlet kit Ø 160   Cod.3.034554

For VICTRIX PRO 180 V2 2 (to discharge at roof)

...

Vertical terminal outlet outdoor kit Ø 160 (stainless steel)   Cod.3.034555

For VICTRIX PRO 180 V2
(for outdoor) length 1m
Technical note: size is not adjustable

...

Anti freeze protection kit -15 °C  VICTRIX PRO V2   Cod.3.034125

Usable in outdoor installations for minimum temperature as low as -15 °C.

...

Condensate discharge pump kit   Cod.3.020002

For single VICTRIX PRO V2

To be used in case of opposite slope between siphon and discharge
It can only be installed inside the building and outside the appliance

...

Condensate neutralizer until 180 kW   Cod.3.033688

Necessary to neutralize the acidity of the condensation. Inclusive of granulate.
...

Condensate neutralizer until 1500 kW   Cod.3.023662

necessary to neutralize the acidity of the condensation. Inclusive of
granulate.

...

Cover kit IPX5D   Cod.3.033689

For VICTRIX PRO 180 V2

...

Dirt separator kit for single installation   Cod.3.033673

For installation both on right and left side

...

Granulate for condensate neutralizer VICTRIX PRO V2   Cod.3.034920

For condensate neutralizer until 180 kW

...

Granulate kit for condensate neutralizer (25 kg)   Cod.3.023663

Complete recharge for condensate neutralizer kit until 1500 kW

...

Hydraulic manifold kit DN 100 for 2 VICTRIX PRO 180 V2 in cascade   Cod.3.034938

Kit to connect 2 VICTRIX PRO 180 V2 in cascade installation; it includes a 2 way interception valve, a 3-way interception valve and a non-return valve for each generator.
Insulation as standard.
...

Hydraulic manifold kit DN 100 for additional VICTRIX PRO 180 V2 in cascade   Cod.3.034939

in combination with kit 3.034938 it serves to connect from 3 to 5 VICTRIX
PRO V2 boilers in cascade installation (one kit required for each additional
boiler); includes a 2-way interception valve, a 3-way interception valve and
a non-return valve. Insulation as standard

...

Hydraulic manifold kit for VICTRIX PRO 100/120/150 /180V2   Cod.3.023952

Specially sized for large thermal systems with high water content.
Equipped with sludge collection filter on the return pipe.
Insulation as standard

...

Hydraulic separator for 100 kW installations   Cod.3.020839

Separator with G 2 ½" threaded connectors.
Insulation as standard.
...

Hydraulic separator for 200 kW installations   Cod.3.021377

Separator with G 2 ½" threaded connectors.
Insulation as standard.
...

Hydraulic separator for 350 kW installations   Cod.3.023965

Separator with threaded connectors - DN 100.
Insulation as standard.
...

Hydraulic separator for 400 kW installations   Cod.3.021378

Separator with G 2 ½" threaded connectors on boiler side - DN 100 on system side.
Insulation as standard.
...

Hydraulic separator for 600 kW installations   Cod.3.023962

Separator with threaded connectors - DN 100.
Insulation as standard.
...

IPX4D protection box kit for cascade safety kit   Cod.3.024038

...

IPX4D protection box kit for single boiler safety kit VICTRIX PRO V2   Cod.3.024028

...

Magnetic dirt separator kit for VICTRIX PRO 100/120/150/180 V2 in cascade   Cod.3.033675

 The kit includes connection manifolds and support.

...

Plate heat exchanger kit for cascade installation on the right side of VICTRIX PRO 100/120/150/180 V2   Cod.3.033679

The kit includes connecting pipes, air vent, discharge tap, filling taps and connection to expansion vessel

...

Plate heat exchanger kit for single installation on the right side of VICTRIX PRO 100/120/150/180 V2   Cod.3.033677

The kit includes connecting pipes, air vent, discharge tap, filling taps and
connection to expansion vessel 

...

Probe kit for PT 1000 solar collector   Cod.3.019374

Used to manage solar plant paired to boiler configurations with cascade
and zone regulator kit

...

Safety kit DN 100 for VICTRIX PRO 100/120/150/180 V2 in cascade   Cod.3.023961

the kit includes thermometer, thermometer holder, lock, thermostat with
manual reset, connection tap for pressure gauge, manual reset pressure
switch, gas intercepting valve trap, expansion vessel connection and
pressure switch for minimum pressure. Insulation as standard

...

Safety kit single boiler VICTRIX PRO V2   Cod.3.023949

The kit includes thermometer, thermometer holder, lock, thermostat with manual reset, connection tap for pressure gauge, manual reset pressure switch, gas intercepting valve trap, expansion vessel connection and pressure switch for minimum pressure. Insulation as standard.
...

Solar collector probe   Cod.3.025467

To be used to manage the solar system coupled to thermal plants using the cascade and zone regulator.
...

Storage tank probe kit   Cod.3.015268

Used to manage the temperature of the water tank unit paired, in boiler
rooms, with cascade and zone regulator kit

...

Three-way valve kit connection to a separate storage tank VICTRIX PRO V2   Cod.3.023950

The kit includes the storage tank probe. The power supply is 230 Vac.
Insulation as standard.

Wall hung, modular condensing boiler for heating only. 

Wide modulating ratio up to 5 boilers in cascade installation, high performances with reduced consumption thanks to the 1:10 modulation range and high efficiency, the new VICTRIX PRO V2 is the ideal solution for light commercial solutions in residential and commercial buildings. The new design, compact and linear, with a vertical sliding door protecting the control board, makes its installation easy even in residential buildings (according to the current regulations in force in each country).
Certified for indoor and outdoor installations, even in unsheltered areas thanks to the IPX5D electric protection, the boiler is supplied with the -5 °C anti-freeze kit as standard.
Thanks to low emissions of carbon monoxide (CO) and nitrogen oxide (NOX), VICTRIX PRO V2 belongs to class 6, the most environmentally-friendly class established by the European standards (UNI EN 297 e UNI EN 483).

The new VICTRIX PRO V2 can work with natural gas, LPG and up to 20% blend of hydrogen.

...

CRONO 7 (weekly digital chronothermostat)   Cod.3.021622

ON/OFF room thermostat.

 

Class of device IV* or VII

Contribution to the environmental heating seasonal energy efficiency 2%* or 3,5%

* default settings

...

CRONO 7 WIRELESS (wireless weekly digital chronothermostat)   Cod.3.021624

Wireless ON/OFF room thermostat.

 

Class of device IV* or VII

Contribution to the environmental heating energy efficiency 2%* or 3,5%

* default settings

...

Cascade and zone regulator kit   Cod.3.034119

It can manage 3 water distribution zones plus an external storage tank unit
and thermal solar for DHW production, both in standalone and cascade
configurations. It includes power supply connection for installation on a DIN
rail.

...

Clip-in for VICTRIX PRO V2   Cod.3.034122

To be used together with Cascade and Zones regulator kit (1 for each boiler).

...

Expansion kit for Cascade and Zones regulator kit   Cod.3.034124

To be used to manage 1 additional zone (direct or mixed) up to a maximum
of 5.

...

External probe   Cod.3.015266

For single installation of VICTRIX PRO V2.
For MAGIS COMBO V2, MAGIS PRO V2, MAGIS COMBO PLUS V2, MAGIS HERCULES PRO, MAGIS HERCULES PRO MINI/EH, TRIO PACK ELECTRIC, TRIO HYDRO system ELECTRIC and MAGIS M/EH.

Temperature control class II*, VI or VII
Contribution to seasonal space heating energy efficiency 2%*, 4 or 3,5%

* default settings

...

External probe kit (for cascade installation)   Cod.3.024511

Paired with cascade and zone regulator kit, it optimizes energy
consumption by adjusting the plant delivery temperature for variable
temperature functioning 

...

Flow probe kit   Cod.3.015267

To be located on the delivery side of the plant, after the hydraulic
separator, it allows the cascade and zone regulator to manage the
delivery temperature of the plant or of the mixed zones available

...

Remote control for single VICTRIX PRO V2   Cod.3.020358

This is a modulating control unit that serves to optimize climatic
management of the temperature in rooms.
It can only be used on systems with a single temperature control.

...

System delivery probe kit for the boiler VICTRIX PRO V2   Cod.3.024245

Connected to the boiler board, it measures the delivery temperature after the hydraulic manifold.

...

Tele-management kit 2.0   Cod.3.034121

It works together with the Cascade and Zones regulator kit. It allows remote
management of the device with a dedicated APP.

...

Zone manager kit   Cod.3.034120

Modulating temperature control, backlit display and remote management of
the zone. It works together with the Cascade and Zones regulator kit.

...

4 extension pipes Ø 160 kit   Cod.3.034559

For VICTRIX PRO 180 V2 0,5 m long

...

4 extension pipes Ø 160 kit   Cod.3.034560

For VICTRIX PRO 180 V2 1 m long

...

4 extension pipes Ø 160 kit   Cod.3.034561

For VICTRIX PRO 180 V2 2 m long

...

4 x 90° bends Ø 160 kit   Cod.3.034563

For VICTRIX PRO 180 V2

...

45° bend Ø 160 kit   Cod.3.034562

For VICTRIX PRO 180 V2 

...

Horizontal kit Ø 160   Cod.3.034556

For VICTRIX PRO 180 V2 (to discharge in the chimney)

...

Horizontal kit Ø 160   Cod.3.034557

For VICTRIX PRO 180 V2 (to discharge horizontally)

...

Stub-pipe kit Ø160 for air intake   Cod.3.034565

for VICTRIX PRO 180 V2 with B23 configuration

...

Terminal vertical outlet kit Ø 160   Cod.3.034554

For VICTRIX PRO 180 V2 2 (to discharge at roof)

...

Vertical terminal outlet outdoor kit Ø 160 (stainless steel)   Cod.3.034555

For VICTRIX PRO 180 V2
(for outdoor) length 1m
Technical note: size is not adjustable

...

Anti freeze protection kit -15 °C  VICTRIX PRO V2   Cod.3.034125

Usable in outdoor installations for minimum temperature as low as -15 °C.

...

Condensate discharge pump kit   Cod.3.020002

For single VICTRIX PRO V2

To be used in case of opposite slope between siphon and discharge
It can only be installed inside the building and outside the appliance

...

Condensate neutralizer until 180 kW   Cod.3.033688

Necessary to neutralize the acidity of the condensation. Inclusive of granulate.
...

Condensate neutralizer until 1500 kW   Cod.3.023662

necessary to neutralize the acidity of the condensation. Inclusive of
granulate.

...

Cover kit IPX5D   Cod.3.033689

For VICTRIX PRO 180 V2

...

Dirt separator kit for single installation   Cod.3.033673

For installation both on right and left side

...

Granulate for condensate neutralizer VICTRIX PRO V2   Cod.3.034920

For condensate neutralizer until 180 kW

...

Granulate kit for condensate neutralizer (25 kg)   Cod.3.023663

Complete recharge for condensate neutralizer kit until 1500 kW

...

Hydraulic manifold kit DN 100 for 2 VICTRIX PRO 180 V2 in cascade   Cod.3.034938

Kit to connect 2 VICTRIX PRO 180 V2 in cascade installation; it includes a 2 way interception valve, a 3-way interception valve and a non-return valve for each generator.
Insulation as standard.
...

Hydraulic manifold kit DN 100 for additional VICTRIX PRO 180 V2 in cascade   Cod.3.034939

in combination with kit 3.034938 it serves to connect from 3 to 5 VICTRIX
PRO V2 boilers in cascade installation (one kit required for each additional
boiler); includes a 2-way interception valve, a 3-way interception valve and
a non-return valve. Insulation as standard

...

Hydraulic manifold kit for VICTRIX PRO 100/120/150 /180V2   Cod.3.023952

Specially sized for large thermal systems with high water content.
Equipped with sludge collection filter on the return pipe.
Insulation as standard

...

Hydraulic separator for 100 kW installations   Cod.3.020839

Separator with G 2 ½" threaded connectors.
Insulation as standard.
...

Hydraulic separator for 200 kW installations   Cod.3.021377

Separator with G 2 ½" threaded connectors.
Insulation as standard.
...

Hydraulic separator for 350 kW installations   Cod.3.023965

Separator with threaded connectors - DN 100.
Insulation as standard.
...

Hydraulic separator for 400 kW installations   Cod.3.021378

Separator with G 2 ½" threaded connectors on boiler side - DN 100 on system side.
Insulation as standard.
...

Hydraulic separator for 600 kW installations   Cod.3.023962

Separator with threaded connectors - DN 100.
Insulation as standard.
...

IPX4D protection box kit for cascade safety kit   Cod.3.024038

...

IPX4D protection box kit for single boiler safety kit VICTRIX PRO V2   Cod.3.024028

...

Magnetic dirt separator kit for VICTRIX PRO 100/120/150/180 V2 in cascade   Cod.3.033675

 The kit includes connection manifolds and support.

...

Plate heat exchanger kit for cascade installation on the right side of VICTRIX PRO 100/120/150/180 V2   Cod.3.033679

The kit includes connecting pipes, air vent, discharge tap, filling taps and connection to expansion vessel

...

Plate heat exchanger kit for single installation on the right side of VICTRIX PRO 100/120/150/180 V2   Cod.3.033677

The kit includes connecting pipes, air vent, discharge tap, filling taps and
connection to expansion vessel 

...

Probe kit for PT 1000 solar collector   Cod.3.019374

Used to manage solar plant paired to boiler configurations with cascade
and zone regulator kit

...

Safety kit DN 100 for VICTRIX PRO 100/120/150/180 V2 in cascade   Cod.3.023961

the kit includes thermometer, thermometer holder, lock, thermostat with
manual reset, connection tap for pressure gauge, manual reset pressure
switch, gas intercepting valve trap, expansion vessel connection and
pressure switch for minimum pressure. Insulation as standard

...

Safety kit single boiler VICTRIX PRO V2   Cod.3.023949

The kit includes thermometer, thermometer holder, lock, thermostat with manual reset, connection tap for pressure gauge, manual reset pressure switch, gas intercepting valve trap, expansion vessel connection and pressure switch for minimum pressure. Insulation as standard.
...

Solar collector probe   Cod.3.025467

To be used to manage the solar system coupled to thermal plants using the cascade and zone regulator.
...

Storage tank probe kit   Cod.3.015268

Used to manage the temperature of the water tank unit paired, in boiler
rooms, with cascade and zone regulator kit

...

Three-way valve kit connection to a separate storage tank VICTRIX PRO V2   Cod.3.023950

The kit includes the storage tank probe. The power supply is 230 Vac.
Insulation as standard.

Related products

VICTRIX PRO 100 V2 EU
Wall-hung modular condensing boiler for heating only

Contacts

Contact us
Customer Care